S. Domański, M. Gryziński, M. Maciak, Ł. Murawski, P. Tulik, K. Tymińska (2016)
Experimental investigation on radiation shielding of high performance concrete for nuclear and radiotherapy facilitiesPolish Journal of Medical Physics and Engineering, 22
M. Zielczyński, N. Golnik, M. Gryziński, P. Tulik (2010)
The use of recombination chambers at radiation therapy facilitiesRadiation Measurements, 45
N. Golnik, K. Pytel (2006)
Irradiation Facilities for BNCT at Research Reactor MARIA in Poland
M. Zielczyński, M. Gryziński, N. Golnik (2007)
Method for determination of gamma and neutron dose components in mixed radiation fields using a high-pressure recombination chamber.Radiation protection dosimetry, 126 1-4
Abstract This paper presents the results on radiation shielding of special types of concrete, designed for nuclear reactor containments. The research focused on the study of shielding properties against neutron component of ionizing radiation. For this purpose, two types of ionizing source were used: the isotopic reference neutron field of 239Pu-Be in calibration laboratory and the MARIA Research Reactor. INTRODUCTION As a measure of effectiveness of a given shield, a half-value layer (HVL) and tenth-value layer (TVL) were used. In addition, attenuation curves (for total dose, gamma and neutron dose components) were set for each of the investigated concrete shields. GW2 and REM-2 ionization chambers were used to collect data, and additionally F1 ionization chamber was utilized during measurements performed at the MARIA reactor to monitor the beam stability in time. Based on the measurements data, for each set of concrete samples, attenuation curves were determined. To distinguish the radiation components (n-γ), the twin detector method was used. As a detector insensitive to the neutron radiation, a hydrogen free GW2 chamber filled with CO2 was used. REM-2 high-pressure, tissue equivalent recombination chamber was used as a detector sensitive to both components of mixed radiation—neutron and gamma(1, 2). Finally, a combination of twin detector and recombination methods was utilized to distinguish dose components and to estimate the radiation quality behind the shield (recombination index of radiation quality RIQ)(3). This work was aimed at developing a method to evaluate the effectiveness of neutron radiation shields. Similar effort was done to evaluate new concrete mixes shielding properties in gamma radiation(4). MATERRIALS AND METHODS The measurement in standard neutron 239Pu-Be calibration source was carried out in Radiation Protection Measurement Laboratory (at National Centre for Nuclear Research, Poland) on a specially adapted stand capable of holding the weight of at least 10 concrete slabs of a total weight up to 300 kg(4, 5). During the investigation 30 mixes of special concrete were measured (in four measurement series) in calibration laboratory and 8 of them (second series) were additionally measured in reactor radiation field. Aggregate composition of examined concrete mixes are shown in Table 1. Table 1. Concrete mixes composition. Aggregate and grain size B11 B12 B13 B14 B15 B16 B17 B18 Sand 0–2 mm + + + + − + + + Serpentinite 0–2 mm − + − − − − − − Serpentinite 2–8 mm − + + + − − + + Serpentinite 8–16 mm − + − + − − − + Magnetite 0–5,6 mm + − + + − − − − Magnetite 0–16 mm + − + − − − − − Barite 0–16 mm − − − − + + + + Density (kg/m3) 3479 2289 3089 2708 3328 3168 2825 2606 Aggregate and grain size B11 B12 B13 B14 B15 B16 B17 B18 Sand 0–2 mm + + + + − + + + Serpentinite 0–2 mm − + − − − − − − Serpentinite 2–8 mm − + + + − − + + Serpentinite 8–16 mm − + − + − − − + Magnetite 0–5,6 mm + − + + − − − − Magnetite 0–16 mm + − + − − − − − Barite 0–16 mm − − − − + + + + Density (kg/m3) 3479 2289 3089 2708 3328 3168 2825 2606 Table 1. Concrete mixes composition. Aggregate and grain size B11 B12 B13 B14 B15 B16 B17 B18 Sand 0–2 mm + + + + − + + + Serpentinite 0–2 mm − + − − − − − − Serpentinite 2–8 mm − + + + − − + + Serpentinite 8–16 mm − + − + − − − + Magnetite 0–5,6 mm + − + + − − − − Magnetite 0–16 mm + − + − − − − − Barite 0–16 mm − − − − + + + + Density (kg/m3) 3479 2289 3089 2708 3328 3168 2825 2606 Aggregate and grain size B11 B12 B13 B14 B15 B16 B17 B18 Sand 0–2 mm + + + + − + + + Serpentinite 0–2 mm − + − − − − − − Serpentinite 2–8 mm − + + + − − + + Serpentinite 8–16 mm − + − + − − − + Magnetite 0–5,6 mm + − + + − − − − Magnetite 0–16 mm + − + − − − − − Barite 0–16 mm − − − − + + + + Density (kg/m3) 3479 2289 3089 2708 3328 3168 2825 2606 239Pu-Be neutron source and the chamber were located in a precisely defined geometry in distance of 1.38 m. In this space, a set of concrete slabs, each 5 cm thick, was placed, thus increasing the thickness of the shielding. Using recombination chambers the dose rate after passing through the shielding was measured. Due to the level of scattered radiation, examination ended when about 10 times the dark current of the chamber was achieved. As the basic quantity for plotting the attenuation curves, the absorbed dose rate was used (determinated by the much lower uncertainty, than equivalent dose), and then using received data the HVL was calculated. Similar to the 239Pu-Be source shield testing, it was decided to use twin detector method using REM-2 and GW2 recombination chambers at the MARIA research reactor(6). Additionally, for monitoring of the reactor source stability, a F1 ionization chamber was used. The H2 is one of the eight horizontal channels located at MARIA Research Reactor in Świerk. Due to its location and construction, it was needed to design and set special stand, that allows the users to remotely manipulate concrete slabs in and out of the beam, without entering the measurement room for radiation protection reasons(7). The sets of concrete mixes were changed only during technical breaks in reactor work. RESULTS 239Pu-Be Shielding Results In order to determine the HVL thickness of each concrete mix, it was necessary to carry out measurement with two ionization chambers with different sensitivities to neutron radiation. To designate shielding properties of different concrete mixes, the two recombination chambers, REM-2 and GW2, were alternately set in the neutron radiation field, together with a dedicated computer and data acquisition system. For each concrete mix, three attenuation curves were determined: attenuation curve for total dose rate, for neutron component and for gamma component. Each of the points on the curves was presented in relative ratio: k=D0*/D(d)*, (1)D0* is the dose rate in measured point, and D(d)* is the dose rate with d thickness of concrete. Attenuation factors and curves of each: total dose rate, neutron and gamma composition (for second series) are presented in Figures 1–3. Figure 1. View largeDownload slide 239Pu-Be total dose attenuation curve. Figure 1. View largeDownload slide 239Pu-Be total dose attenuation curve. Figure 2. View largeDownload slide 239Pu-Be neutron dose component attenuation curve. Figure 2. View largeDownload slide 239Pu-Be neutron dose component attenuation curve. Figure 3. View largeDownload slide 239Pu-Be gamma dose component attenuation curve. Figure 3. View largeDownload slide 239Pu-Be gamma dose component attenuation curve. The obtained data can be fitted numerically (e.g. with the polynomial interpolation, least squares methods, all of them gave similar agreement; in the figures, polynomial fitting is shown). From the resulting fitting curve representative HVL values can be obtained. Note that neutron backscattering was not considered in this measurements, but they were included in the determination of uncertainty. The received HVL for neutron composition of 239Pu-Be source in comparison with 137Cs HVL are presented in Table 2. The uncertainties of each of neutron HVL values does not exceed 15% (for neutron dose measurement 10%), for 137Cs—10% (gamma dose determination 7%). Table 2. HVL values of different concrete mixes for 239Pu-Be neutron component in comparison with 137Cs(4). HVL (cm) 137Cs 239Pu-Be B11 2.67 9.04 B12 4.34 10.27 B13 3.17 10.4 B14 3.71 10.87 B15 2.8 11.05 B16 2.86 8.93 B17 3.27 10.7 B18 3.65 10.58 HVL (cm) 137Cs 239Pu-Be B11 2.67 9.04 B12 4.34 10.27 B13 3.17 10.4 B14 3.71 10.87 B15 2.8 11.05 B16 2.86 8.93 B17 3.27 10.7 B18 3.65 10.58 Table 2. HVL values of different concrete mixes for 239Pu-Be neutron component in comparison with 137Cs(4). HVL (cm) 137Cs 239Pu-Be B11 2.67 9.04 B12 4.34 10.27 B13 3.17 10.4 B14 3.71 10.87 B15 2.8 11.05 B16 2.86 8.93 B17 3.27 10.7 B18 3.65 10.58 HVL (cm) 137Cs 239Pu-Be B11 2.67 9.04 B12 4.34 10.27 B13 3.17 10.4 B14 3.71 10.87 B15 2.8 11.05 B16 2.86 8.93 B17 3.27 10.7 B18 3.65 10.58 MARIA Reactor H2 Horizontal Channel Results For a number of selected sets of concrete mixes, the measurement campaign in the real reactor radiation field at the outlet of the horizontal channel H2 of MARIA reactor was conducted. Due to the special and complex nature of this kind of source, such as reactor, it was decided to give up HVL and focused on the attenuation curves determination. HVL in this case is not a good indicator for shielding properties. Attenuation curves are giving more information about in depth changes of the radiation within the shield. The measurements showed that for thick shields HVL does not show adequate shield effectiveness. In Figures 4–6, the results of the same concrete mixes as in 239Pu-Be source are presented. Figure 4. View largeDownload slide H2 horizontal channel total dose attenuation curve. Figure 4. View largeDownload slide H2 horizontal channel total dose attenuation curve. Figure 5. View largeDownload slide H2 horizontal channel neutron dose component attenuation curve. Figure 5. View largeDownload slide H2 horizontal channel neutron dose component attenuation curve. Figure 6. View largeDownload slide H2 horizontal channel gamma dose composition attenuation curve. Figure 6. View largeDownload slide H2 horizontal channel gamma dose composition attenuation curve. CONCLUSIONS Finest shielding effectiveness in 239Pu-Be source in examined concrete mixes were for concrete containing barite (B16) and magnetite (B11) aggregates—the HVL obtained was about 9 cm. This value may be changed with depth due to radiation attenuation. There was no any simple correlation between the amount or type of the aggregate. The difference may have been distinguished only between light (serpentinite) and heavy (barite/magnetite) aggregate components. In source containing more thermalized neutron spectrum—H2 horizontal channel, mixes with high density (B11, B15, B16) provided finest results. Low gamma composition attenuation factor in both cases is due the secondary gamma produced by weakening of the neutron radiation component and creating secondary gamma. Relatively low gamma attenuation in neutron sources must be considered in design of proper shielding in both medical and nuclear facilities that uses neutron radiation. FUNDING This work was supported by the National Centre for Research and Development [PB/A2/15/2014]. REFERENCES 1 Zielczyński , M. and Golnik , N. Rekombinacyjne komory jonizacyjne, Monografie IEA ( 2000 ). 2 Zielczyński , M. et al. . The use of recombination chambers at radiation therapy facilities . Radiat. Meas. 45 , 1472 – 1475 ( 2010 ). Google Scholar CrossRef Search ADS 3 Zielczyński , M. , Gryziński , M. A. and Golnik , N. Method of determination of gamma and neutron dose components in mixed radiation fields using a high-pressure recombination chamber . Radiat. Prot. Dosim. 126 ( 1–4 ), 306 – 309 ( 2007 ). Google Scholar CrossRef Search ADS 4 Domański , S. et al. . Experimental investigation on radiation shielding of high performance concrete for nuclear and radiotherapy facilities . Polish J. Med. Phys. Eng. 22 ( 2 ), 41 – 47 ( 2016 ). Google Scholar CrossRef Search ADS 5 Burakowska , A. et al. . Radiation shielding examination of special concretes . J. Civil Eng. Environ. Archit. , t. XXXIII z. 63 , 87 – 96 ( 2016 ). 6 Golnik , N. and Pytel , K. Irradiation facilities for BNCT at Research Reactor Maria in Poland . Polish J. Med. Phys. Eng. 12 ( 3 ), 143 – 153 ( 2006 ). 7 Murawski , Ł. , Gryziński , M. A. and Tymińska , K. Research Stand for Concrete Shielding Tests, RAD2015 Proceedings, 199–201 ( 2015 ). © The Author(s) 2018. Published by Oxford University Press. All rights reserved. For Permissions, please email: [email protected] This article is published and distributed under the terms of the Oxford University Press, Standard Journals Publication Model (https://academic.oup.com/journals/pages/about_us/legal/notices)
Radiation Protection Dosimetry – Oxford University Press
Published: Aug 1, 2018
Read and print from thousands of top scholarly journals.
Already have an account? Log in
Bookmark this article. You can see your Bookmarks on your DeepDyve Library.
To save an article, log in first, or sign up for a DeepDyve account if you don’t already have one.
Copy and paste the desired citation format or use the link below to download a file formatted for EndNote
Access the full text.
Sign up today, get DeepDyve free for 14 days.
All DeepDyve websites use cookies to improve your online experience. They were placed on your computer when you launched this website. You can change your cookie settings through your browser.