TRANSFORMER WINDING LEAKAGE FIELD EFFECTS AND THEIR CALCULATION

TRANSFORMER WINDING LEAKAGE FIELD EFFECTS AND THEIR CALCULATION This contribution describes for one particular 4590 MVA transformer design the results of finite element calculations of its leakage field and winding forces. The results show that the forces on the end turns and the leakage flux vary significantly with position. On the basis of these results the computation is extended to consider the calculation of the a.c. losses and their distribution. The calculated and measured values are 437 kW and 407 kW. http://www.deepdyve.com/assets/images/DeepDyve-Logo-lg.png COMPEL: The International Journal for Computation and Mathematics in Electrical and Electronic Engineering Emerald Publishing

Loading next page...
 
/lp/emerald-publishing/transformer-winding-leakage-field-effects-and-their-calculation-FQmeOdgwp8

References (1)

Publisher
Emerald Publishing
Copyright
Copyright © Emerald Group Publishing Limited
ISSN
0332-1649
DOI
10.1108/eb051773
Publisher site
See Article on Publisher Site

Abstract

This contribution describes for one particular 4590 MVA transformer design the results of finite element calculations of its leakage field and winding forces. The results show that the forces on the end turns and the leakage flux vary significantly with position. On the basis of these results the computation is extended to consider the calculation of the a.c. losses and their distribution. The calculated and measured values are 437 kW and 407 kW.

Journal

COMPEL: The International Journal for Computation and Mathematics in Electrical and Electronic EngineeringEmerald Publishing

Published: Jan 1, 1992